E45-183 · Grounding and Shielding · Long Shielded Signal Cable · ★★
After the shielded cable was grounded at three brackets, its radiation in the high-frequency band (>10MHz) actually increases and a nearby radio station is disturbed
[Mechanism] More than two grounding points on the shield with unequal potentials form several loops; an external high-frequency field drives current in these loops and the shield turns into a radiating antenna; the multiple points also make the shield currents add in phase and enhance the radiation.
[Calculation] Three grounding points with 1V differences, a loop area of 0.1m², f=30MHz → loop induced voltage e=2πfBA with B=μ₀I/2πr, and the loop current amplifies the radiation; multi-point grounding is only beneficial under the rule λ/20<cable length.
[Design Omission] A long cable was blindly grounded at multiple points, without a grounding strategy based on frequency.
① Low-frequency single end: for signals <1MHz ground the shield at one end only → forms no loop
② High-frequency dual end via capacitor: where high-frequency shielding is needed, ground through a 10nF capacitor → passes high frequency, blocks the low-frequency loop
③ Equipotential to lower the difference: bond the grounding points with copper bar to keep ΔU<0.5V → reduces loop current
④ Fewer points: add no unnecessary grounding points → avoids multiple loops
⑤ Shield continuity: keep the shield unbroken along its length → stays enclosed
⑥ Radiation measurement: measure the radiation margin >6dB from 30-1000MHz → verify it is within limits
⑦ Loop-current test: break the shield loop and measure the current → verify no circulating current
⑧ Write the grounding strategy into the EMC specification → gate at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields