E45-194 · Grounding and Shielding · Fieldbus Cable · ★★
Bus communication works intermittently; inspection shows the shield was worn through by the metal tray and shorted locally to PE
[Mechanism] Once the shield is damaged it randomly touches PE (the tray), creating an unintended ground at the damaged point, so the shield sits at different potentials in several places and circulating currents flow; the damaged spot also lets the signal line short to PE and interrupts communication.
[Calculation] PE contact at the damaged point makes that shield section sit at ground potential, a ΔU=2V difference from the ground at the other end → circulating current; if the signal insulation is also broken it shorts directly to PE and drops the bus node.
[Design Omission] The cable had no protection against the sharp tray edge, and the shield has no continuous jacket.
① Wrap protection: add a rubber grommet where the cable crosses the sharp edge → no abrasion
② Damage check: measure shield-to-ground insulation section by section >10MΩ → locate the damaged point
③ Shield repair: restore shield continuity at the damaged spot with heat-shrink plus copper mesh → keeps it enclosed
④ Single-end grounding: after repair bond the shield to PE at one end only → no circulating current
⑤ Bus termination: check the terminating-resistor match (120Ω) → stable communication
⑥ Node-drop test: bit error rate under full-load communication → verify no node drops
⑦ Tray treatment: fit a protective strip on the tray's inner corner → prevents re-abrasion
⑧ Write cable protection into the wiring rules → gate at the source
GB/T 19666-2019 Flame retardant and fire resistant wires and cables