E45-195 · Grounding and Shielding · Low-Frequency mV Signal Line · ★
A nearby high-current busbar superimposes 50Hz magnetically induced noise (±1%) on a millivolt signal carried on twisted pair alone without shielding
[Mechanism] Twisting counteracts a uniform external magnetic field, but the strong near field of a low-frequency high-current busbar still couples unequally within one twist pitch and produces differential-mode noise; only a shield can terminate the field at the casing and carry it away.
[Calculation] Busbar I=500A at distance d=10cm from the signal line → B=μ₀I/2πd=1mT; the voltage coupled within a twist pitch is e=2πfBA with A≈twist pitch × wire diameter, giving e≈0.3mV ≈ 1% of the signal.
[Design Omission] In a strong magnetic-field environment only twisted pair was used, with no shield added.
① Add shielding: replace the signal line with shielded twisted pair → the field terminates at the shield
② Shield to PE: bond the shield to PE at one end → provides a shielding reference
③ Keep away from the busbar: route the cable >30cm from the high-current busbar → lowers B
④ Orthogonal routing: cross the signal line perpendicular to the busbar → reduces the coupling area
⑤ Ferrite: add a ferrite bead (high μ) on the line → suppresses low-frequency magnetic coupling
⑥ Noise test: measure the signal peak-to-peak <0.1% → verify
⑦ Twist-pitch check: twist pitch <10× wire diameter → cancels a uniform field
⑧ Write the shielding requirement into strong-field routing rules → gate at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields