Knowledge Base › Electrical Sensor Error Case › Functional Earth Not Separated from Protective Earth

Functional Earth Not Separated from Protective Earth

E45-197 · Grounding and Shielding · Precision Measurement Cabinet · ★★

Problem Description

In a precision measurement cabinet the functional earth (signal reference) and the protective earth are mixed, and the reading randomly jumps ±2 counts

Root Cause

[Mechanism] The functional earth carries the weak signal reference while the protective earth carries fault and interference currents; mixing them couples the protective-earth noise onto the functional earth through the shared segment and contaminates the reference; their unequal potentials also form a loop.
[Calculation] Protective-earth interference current I=1A across a shared-segment impedance of 0.01Ω → ΔU=10mV, lifting the functional-earth reference by 10mV, far above the microvolt-level signal.
[Design Omission] The cabinet has no separate functional-earth and protective-earth bars; they are mixed at the common termination.

Corrective Solution

① Separate bars: provide distinct functional-earth and protective-earth copper bars in the cabinet → no cross-coupling
② Single-point bonding: link the two bars only through a Y capacitor / single point → passes high frequency, blocks mains frequency
③ Floating functional earth: keep the functional earth floating with a single reference point → immune to PE noise
④ Heavier protective earth: use ≥16mm² for the protective-earth bar → low-resistance fault dissipation
⑤ Isolated supply: power the functional circuits from an isolated supply → decouples ground from PE
⑥ Reference measurement: measure the functional-earth ripple <10μV → verify it is clean
⑦ Count-jump ratio: no-load reading jumps <1 count → verify
⑧ Write the separate-bar requirement into the cabinet grounding diagram → gate at the source

Checklist

Reference

GB/T 2887-2011 General specification for computer field