E45-202 · Grounding and Shielding · Control Cabinet Interior · ★
The potential difference between equipment enclosures inside the cabinet reached 3V, and interconnecting signals produced occasional interference
[Mechanism] With no continuous equipotential copper bar inside the cabinet, each equipment enclosure is grounded to a different nearby PE point through its own cable; the in-cabinet potentials differ, giving differential-mode noise on interconnected signals, and the lack of continuity also leaves cabinet sections floating.
[Calculation] An enclosure bonded to an outside PE point through a long cable, with 0.05Ω × 5A interference current, gives ΔU=0.25V per device, accumulating to 3V across several devices.
[Design Omission] There was no unified equipotential bar in the cabinet and the enclosures were grounded separately.
① Continuous bar: fit a continuous equipotential copper bar inside the cabinet (≥25×3mm) → one reference
② Device tie-in: bond each enclosure to the bar with a short lead → small ΔU
③ Bar to PE: bond the bar to the outside PE at one point → reliable
④ Short leads: device-to-bar leads <0.3m → less resistance
⑤ Potential test: ΔU between enclosures <0.1V → confirmed
⑥ Interference comparison: noise on interconnected signals falls → confirmed
⑦ Torque check: joint torque ≥2.5N·m → secure
⑧ Write the equipotential bar into the cabinet design → control at the source
GB/T 25295-2010 Guidelines for safety design of electrical equipment