E45-201 · Grounding and Shielding · Thermocouple Temperature System · ★★
The thermocouple system's zero drifted ±3℃ with the seasons, and its several grounding points were at different potentials
[Mechanism] When the signal loop (including compensation and extension leads) is grounded nearby at several points, the potential differences between those points add up as common mode along the loop; converted to differential mode by imbalance, they add to the thermoelectric voltage and show up as zero drift.
[Calculation] With ΔU=2V between two grounding points and a 1Ω loop imbalance resistance, the differential Δu≈2mV, equivalent to about 50℃ (40μV/℃); the measured ±3℃ reflects a local imbalance.
[Design Omission] The compensation lead was grounded again at an intermediate junction box, creating multi-point grounding.
① Single-point grounding: ground the signal loop only at the display end → no multi-point loop
② Isolation module: insert an isolating transmitter in the middle → breaks the ground loop
③ Equipotential bonding: bond the junction-box enclosures to equal potential → small ΔU
④ Single-end shield: ground the compensation lead's shield at one end → no loop
⑤ Cold-junction compensation: use integrated cold-junction compensation → no reliance on multi-point references
⑥ Zero test: short the input and measure zero drift <0.5℃ → confirmed
⑦ Potential test: ΔU between grounding points <0.5V → confirmed
⑧ Write single-point grounding into the temperature-measurement system drawing → control at the source
GB/T 16839.1-1997 Thermocouples - Part 1: Reference tables