E45-204 · Grounding and Shielding · Encoder Feedback Cable · ★★
The encoder count on large equipment jumped by ±tens of pulses occasionally, together with equipment start and stop
[Mechanism] When large equipment starts or stops the ground-grid potential transients; the potential difference between the encoder and the controller changes abruptly, forming a common-mode surge through the feedback cable's shield or return wire that couples into the differential signal and causes miscounting.
[Calculation] At start/stop the ground-potential difference ΔU=5V lasting 1ms momentarily exceeds the interface common-mode range of ±7V and causes erroneous reception; multi-point shield grounding amplifies the surge.
[Design Omission] The encoder cable shield was grounded at several points and the common-mode transient was not isolated.
① Isolated interface: use magnetic isolation for the encoder (1500V) → the common-mode surge does not couple through
② Single-end shield: bond the shield to PE at the controller end only → no transient loop
③ Equipotential bonding: bond the encoder and controller enclosures to equal potential → small ΔU
④ Differential transmission: use RS422 differential → small common-to-differential conversion
⑤ Common-mode range: interface common mode ≥±15V → tolerates transients
⑥ Jump test: count jump <±1 at start/stop → confirmed
⑦ Potential-difference test: ΔU between the two points <1V → confirmed
⑧ Write the grounding method into encoder wiring → control at the source
GB/T 14479-2010 Electrical safety of machinery — Sensors