E45-205 · Grounding and Shielding · Analog Signal Line · ★
The shield was landed on the grounding terminal beside the inverter, and the signal noise became even worse than before
[Mechanism] The shield should be grounded at a single low-noise point (at the receiving device) to establish a quiet reference; grounded instead at a high-noise point (inverter PE, beside high-current equipment) that noise couples straight into the signal line through the shield, and the shield becomes a noise antenna.
[Calculation] With a 4V noise-point potential ΔU and a shield capacitance C=50pF coupling to the signal, the induced Δu doubles the noise compared with the original.
[Design Omission] The installer grounded the shield at the nearest point without choosing a quiet one.
① Quiet-point grounding: land the shield on a clean PE point at the receiving device → establishes a quiet reference
② Away from noise: keep the grounding point ≥1m from the inverter → less noise
③ Single-end grounding: ground at the receiving end only → no circulating current
④ Mark the grounding point: show the shield grounding point on the drawing → prevents random grounding
⑤ Twisted pair: use twisted-pair cable for the signal → less common-to-differential conversion
⑥ Noise comparison: noise falls >50% after regrounding → confirmed
⑦ Point test: measure the grounding point's noise potential <0.5V → quiet confirmed
⑧ Write the grounding point into the wiring drawing → control at the source
GB 50217-2018 Standard for design of cables of electric power engineering