Cable Tray Not Bonded Across Sections - Electrical Discontinuity

E45-206 · Grounding and Shielding · Cable Tray · ★

Problem Description

The tray sections were not bonded across the joints, so the shielding effectiveness dropped for the shielded cables passing through and high frequencies coupled in

Root Cause

[Mechanism] The cable tray should act as a continuous shield, with bonding jumpers across the sections to keep it electrically continuous; without jumpers the tray is broken at the joints, forming a leakage slot outside the shield through which external fields enter.
[Calculation] A 1m joint with no jumper leaves that tray section electrically broken, and a 30MHz field leaks in, inducing an extra e=2πfBA in the shielded cables inside.
[Design Omission] Each tray section was installed independently with no bonding jumpers and no overall earthing.

Corrective Solution

① Bonding continuity: connect each tray section with ≥4mm² jumpers → electrically continuous
② Overall earthing: bond the tray to PE at at least two points along its run → low-impedance shield
③ Flexible bonding: bond moving sections with braided flexible copper strap → movable yet continuous
④ Lap-face preparation: strip paint and rust-proof the lap faces → good contact
⑤ Shielding test: measure the SE of shielded cables inside the tray with no drop → confirmed
⑥ Joint check: inspect every joint for a bonding jumper with none missed → confirmed
⑦ Earthing test: tray-to-earth resistance <0.1Ω → confirmed
⑧ Write the bonding-jumper requirement into the tray installation specification → control at the source

Checklist

Reference

GB 50303-2015 Code for acceptance of construction quality of building electrical engineering