Knowledge Base › Electrical Sensor Error Case › Multi-Point Shield Grounding Amplifies Resonance

Multi-Point Shield Grounding Amplifies Resonance

E45-208 · Grounding and Shielding · Long Shielded Cable · ★★

Problem Description

After the shield was grounded at several points, noise at one band (about 2MHz) showed a peak instead of falling

Root Cause

[Mechanism] A multi-point-grounded shield together with its grounding leads forms an LC resonant circuit; near the resonant frequency its impedance is lowest and the circulating current largest, so external-field excitation amplifies rather than suppresses noise at that frequency.
[Calculation] With shield L≈1μH and grounding stray C≈25pF, the resonance f=1/(2π√LC)≈1MHz, the same order as the measured 2MHz, and the circulating current is amplified at resonance.
[Design Omission] Multi-point grounding was applied blindly without evaluating the resonant frequency.

Corrective Solution

① Low frequency, one end: for signals <1MHz ground the shield at one end only → avoids resonance
② Capacitive grounding at high frequency: where multiple points are needed, ground through a 10nF capacitor → shifts the resonance
③ Equipotential bonding: bring all grounding points to equal potential → reduces the circulating current
④ Fewer points: do not add grounding points unless necessary → avoids the loop
⑤ Resonance test: sweep the noise spectrum and find no peak → confirmed
⑥ Continuous shield: keep the shield unbroken → keeps it closed
⑦ Frequency avoidance: size the grounding conductors so the resonance is >10MHz → stays out of band
⑧ Write the grounding strategy into the EMC specification → gate at the source

Checklist

Reference

GB/T 17626.3-2016 Radiated radio-frequency electromagnetic field immunity test

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL