E45-209 · Grounding and Shielding · Outdoor Equipotential Bonding Point · ★★
Two years after commissioning the equipotential terminal had corroded, the inter-cabinet potential difference rose back to 5V, and communication dropped out occasionally
[Mechanism] In a damp, corrosive environment the equipotential terminal oxidises into a high-resistance layer, the contact resistance rises, the equipotential bond fails, and the inter-cabinet potential difference returns as common-mode interference.
[Calculation] The oxide layer raises the contact resistance from <0.1Ω to 2Ω, and the ground-potential difference is injected straight into the signal through it, giving 5V of common mode.
[Design Omission] The terminal used no corrosion-resistant material and had no protection, and was kept in a damp environment long term.
① Corrosion-resistant terminal: use stainless-steel or tinned-copper terminals → resists corrosion
② Protective treatment: coat the terminal with conductive paste to prevent oxidation → stable contact
③ Sealed box: fit a sealed junction box at the bonding point → moisture protection
④ Periodic check: measure contact resistance quarterly, <0.1Ω → early detection
⑤ Redundant bonding: use two bonding conductors in parallel → no single-point failure
⑥ Potential test: measure the inter-cabinet ΔU <0.5V → recovery confirmed
⑦ Derust and retighten: grind the corroded point and retorque it → restored
⑧ Write the protection requirement into outdoor grounding maintenance → control at the source
GB 50169-2016 Electrical installation engineering — Construction and acceptance code for grounding installations