Knowledge Base › Electrical Sensor Error Case › Repeated PE Earthing Causes Circulating Current

Repeated PE Earthing Causes Circulating Current

E45-216 · Grounding and Shielding · Long-Run PE System · ★★

Problem Description

The PE conductor was earthed repeatedly at several points, and a circulating current measured on the PE made precision equipment jitter

Root Cause

[Mechanism] The PE conductor should be bonded to the ground grid at one point; repeated earthing at several points makes the differing ground potentials drive a circulating current along the PE trunk, and that current produces a voltage drop in the shared section that pollutes the equipment ground.
[Calculation] With ΔU=2V between two earthing points and a PE resistance of 0.01Ω, the circulating current I=200A; it produces a significant voltage drop in the equipment's bonding section and hence common-mode interference.
[Design Omission] In a blind pursuit of reliable earthing, PE was repeatedly bonded at several points, forming a ground loop.

Corrective Solution

① Single-point PE: bond the PE trunk to the ground grid at the supply end only → no loop
② Equipotential bonding: bond equipment together via an equipotential bar instead of repeated PE earthing → removes the difference
③ Star arrangement: bring each equipment's PE separately to the main bar → no shared section
④ Loop test: measure the circulating current on the PE trunk ≈0 → confirmed
⑤ Potential difference: ΔU between earthing points <0.5V → confirmed
⑥ Isolation: add signal isolators → no common-mode coupling
⑦ Thick trunk: PE trunk ≥25mm² → low resistance
⑧ Write the earthing principle into the PE system diagram → control at the source

Checklist

Reference

GB 50303-2015 Code for acceptance of construction quality of building electrical engineering

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL