E45-224 · Grounding and Shielding · Cabinet Grounding Busbar · ★
The connection points of the cabinet grounding busbar oxidised, the equipment ground potential floated, and the signal picked up occasional interference
[Mechanism] Oxidation at the busbar joints forms a high-resistance copper-oxide layer, raising the contact resistance; the reference potential of equipment grounded through it floats, and noise and ground-potential differences are introduced as common mode through that high resistance.
[Calculation] Oxidation raises the contact resistance from <0.01Ω to 0.5Ω; an interference current of 1A gives a floating ΔU=0.5V, causing common-mode interference.
[Design Omission] The busbar joints were not tinned, no conductive paste was applied, and they were kept in a damp environment.
① Tinning: tin the busbar joint faces → oxidation-resistant
② Conductive paste: apply conductive paste to the lap faces → lower contact resistance
③ Torque to spec: joint-bolt torque ≥2.5N·m → firm contact
④ Periodic check: measure each joint's contact resistance every six months, <0.05Ω → early detection
⑤ Moisture sealing: mount the busbar in a dry area or paint it → moisture protection
⑥ Potential test: equipment ground potential floats <0.1V → confirmed
⑦ Oxidation check: no green corrosion on the joint faces → confirmed
⑧ Write busbar maintenance into cabinet maintenance → control at the source
GB 50169-2016 Electrical installation engineering — Construction and acceptance code for grounding installations