E45-226 · Wiring and Terminals · Two-Wire Transmitter · ★
After the 4-20mA transmitter was wired in reverse, the output was 0 or negative and the PLC reading fell below 4mA, reporting a broken wire
[Mechanism] A two-wire transmitter shares the same two wires for power and signal; with reversed polarity the internal protection keeps the device from working, the output current is clamped at 0 or only leakage current, and below the 4mA lower limit it is read as a broken wire.
[Calculation] Reverse 24V across the protection diode clamps the current <0.1mA, far below the 4mA lower limit; if the protection fails, the power-supply chip burns out.
[Design Omission] No polarity colour coding was provided, there was no reverse-polarity protection circuit, and the wiring diagram was unclear.
① Polarity colour coding: brown +, blue -, plus terminal polarity marks → prevents mix-ups
② Reverse protection: series blocking diode or full-bridge rectifier → reverse connection does no harm
③ Clear diagram: mark the supply polarity clearly and wire per the drawing → no mistake
④ Power-up test: measure the current, 4-20mA → correct polarity confirmed
⑤ Broken-wire alarm: alarm when current <3.8mA → early detection
⑥ Briefing: verify polarity before wiring → no reversal
⑦ No-load test: measure at no load first, then under load → confirmed
⑧ Write polarity verification into the wiring card → control at the source
GB 50254-2014 Electrical installation engineering — Construction and acceptance code for low-voltage electrical apparatus