E45-227 · Wiring and Terminals · Thermocouple Junction Box · ★
The thermocouple signal suddenly dropped out during operation; on opening the cover the stranded wire was found to have pulled straight out of the terminal
[Mechanism] The stranded flexible wire was screwed directly into the terminal without a crimp ferrule, so the screw held only loose strands; vibration fatigued and broke the strands, some pulled out, and contact made and broke until it failed completely open.
[Calculation] The loose strands left only 30% of the original effective cross-section, tripling the current density and accelerating oxidation through heating; after 200 vibration cycles the strand breakage rate reached 60%.
[Design Omission] No crimp ferrule was matched to the wire gauge, no crimping tool was used to compress it, and the termination practice was not standardised.
① Fit a crimp ferrule: choose an OT/UT terminal to suit the wire gauge → matched
② Crimp properly: use a crimping tool until the ferrule is fully deformed → it will not pull out
③ Pull test: after crimping the pull-out force ≥50N → secure
④ Two strands max: no more than 2 conductors in the terminal → no crowding
⑤ Termination process: write a wiring work instruction → standardised
⑥ Vibration test: simulate vibration with no pull-out → confirmed
⑦ Cover-off inspection: check periodically for stray strands → early prevention
⑧ Write termination practice into the process card → control at the source
GB/T 19678.1-2010 Bare terminals, wire-end ferrules and conduits — Technical requirements and tests