E45-228 · Wiring and Terminals · Terminal Block · ★
A 4mm² conductor was fitted into a 2.5mm² terminal; in service the terminal temperature rose by 45℃ and gave off a burning smell
[Mechanism] The conductor cross-section exceeds the terminal's rated clamping range, so the screw cannot compress all the strands; the effective contact area is insufficient, the contact resistance is too high, and the current flow heats it by Joule heating.
[Calculation] The contact resistance rose from 0.01Ω to 0.08Ω; at 10A the dissipation is P=I²R=8W, and the temperature rise ΔT≈Rθ·P reaches 45℃, out of spec.
[Design Omission] The terminal block selection did not check the conductor cross-section, left no margin, and did not verify the current-carrying capacity.
① Terminal match: choose a terminal whose bore suits the wire gauge → proper compression
② Current check: terminal rated current ≥1.2 times the wire current → no overload
③ Temperature test: in service the terminal temperature rise <40K → confirmed
④ Derating: if over the limit, fit a larger terminal or parallel the conductors → lower resistance
⑤ Contact resistance: measure <0.05Ω → good connection confirmed
⑥ Regular IR scan: measure the terminal temperature with an infrared camera → early warning
⑦ Clear labelling: mark the applicable wire gauge on the terminal → prevents mistakes
⑧ Write terminal selection into the parts list → control at the source
GB/T 14048.7-2016 Low-voltage switchgear and controlgear — Ancillary equipment — Terminal blocks for copper conductors