The end of the encoder's stranded shielded cable splayed open, and some strands touched the adjacent position, causing occasional short circuits
[Mechanism] After stripping, a stranded flexible wire that is neither tinned nor fitted with a ferrule splays open; under screw pressure the fine copper strands flare outward, and neighbouring strands bridge to the adjacent terminal, causing momentary shorts or signal crosstalk.
[Calculation] A single 0.2mm² strand carries only 0.5A; during a short the transient current pulls down the potential at the adjacent point, the encoder A/B phases flip falsely, and the count goes wrong.
[Design Omission] The stranded-wire ends were neither tinned nor crimped, the strip length was too long, and no insulation protection was applied.
① Tinning: tin the ends of the stranded wire → no splaying
② Crimp alternative: or fit crimp ferrules → neat ends
③ Short strip: strip length ≤8mm → no exposed strands
④ Heat-shrink: add heat-shrink tubing at the end → insulation
⑤ Gap check: no strand bridges to the adjacent position → confirmed
⑥ Tightening test: no strand flares after tightening → secure
⑦ Visual inspection: check periodically for stray strands → early prevention
⑧ Write the termination process into the work instruction → control at the source
GB/T 13140.1-2008 Connecting devices for low-voltage circuits for household and similar purposes