E45-236 · Wiring and Terminals · Motor Temperature PTC · ★
The PTC temperature-sensing wire suddenly broke in service and the motor overheat protection failed
[Mechanism] Fine stranded wire was pushed straight into the spring terminal with no ferrule, so the spring force acted on only a few strands; long-term thermal cycling crept and relaxed the clamping point and the contact resistance grew until the circuit opened.
[Calculation] The number of effectively clamped strands fell from 19 to 6 and the contact resistance rose from 0.02Ω to 0.3Ω; at 10mA the 3mV drop made the PTC threshold misjudge and finally break.
[Design Omission] No ferrule matched to the wire gauge, the spring terminal was not selected for the right wire size, and no pull test.
① Fit a ferrule: crimp a ferrule onto fine wire → full clamping
② Gauge matching: select the correct wire-size range for the spring terminal → firm clamp
③ Pull test: pull-out force ≥30N → confirmation
④ Inspection: check periodically for no loosening → early prevention
⑤ Redundant wiring: use redundant temperature-sensing wires → no missed fault
⑥ Break alarm: alarm on a PTC break → early warning
⑦ Temperature verification: measure the contact temperature in service → confirmation
⑧ Write the ferrule matching into the process → control at the source
GB/T 19678.1-2010 Bare terminals, wire-end ferrules and conduits — Technical requirements and tests