E45-235 · Wiring and Terminals · Power Terminal Block · ★
Several loads were paralleled on one terminal; in service the terminal charred and melted open and the whole cabinet lost power
[Mechanism] A single terminal has a limited current rating; the combined current of several loads exceeds it, the dissipation at the contact point rises as I²R, the temperature rise exceeds what the insulation can take, and the terminal chars until it melts open.
[Calculation] A terminal rated 15A carried 38A, 2.5 times its rating; the dissipation rose from 3.4W to 21.8W and the temperature rise ΔT exceeded 120℃, melting the solder.
[Design Omission] The total current was not evaluated, no splitting of the load, and the terminal block was undersized.
① Split the load: spread the total current over several terminals → within rating
② Rating check: terminal rating ≥1.5 times the total current → margin
③ Temperature-rise measurement: rise in service <40K → confirmation
④ Paralleling: use copper lugs for high currents → secure
⑤ Infrared survey: measure the terminal temperature with an IR camera → early warning
⑥ Current labels: label the current of each branch → no guesswork
⑦ Load reduction: if exceeded, add terminals or another block → reduce
⑧ Write the current calculation into the schedule → control at the source
GB/T 14048.7-2016 Low-voltage switchgear and controlgear — Ancillary equipment — Terminal blocks for copper conductors