E45-234 · Wiring and Terminals · Outdoor Level Gauge · ★
The leads in the junction box were left too short; the cover pressed on them, the cores broke, and the level signal was lost completely
[Mechanism] With too little slack inside the junction box, closing the cover squeezed and bent the leads; the repeated thermal expansion and contraction fatigued the metal at the bend until it broke and opened the signal circuit.
[Calculation] With slack <30mm the bend radius is <5mm and the bending stress in the copper exceeds yield; after 300 temperature cycles strands begin to break until the wire fails completely.
[Design Omission] No wiring slack left, no wire securing, and cramped space inside the box.
① Leave slack: keep ≥80mm of spare wire in the box → not taut
② Wire clips: secure the leads in the box with cable ties → no swinging
③ Bend radius: bend radius ≥6 times the cable diameter → no kinking
④ Careful closing: close the cover without pinching the wires → no squeezing
⑤ Continuity test: check the circuit is continuous after wiring → confirmation
⑥ Periodic open-up inspection: check the spare wire for no kinks → early prevention
⑦ Slack standard: set the slack in the process → conform
⑧ Write the wiring slack into the drawing → control at the source
GB/T 3797-2016 Electrical control equipment