E45-238 · Wiring and Terminals · VFD Cabinet Terminal · ★
The VFD output terminal blackened after half a year in service and tripped on overcurrent occasionally
[Mechanism] The terminal screw was not torqued to the specified value, so the microscopic contact points were under-compressed and the true contact area was small; under high current the contact point heats up, oxidation accelerates, the resistance rises further, and a vicious circle forms.
[Calculation] The torque was only 0.3N·m, far below 0.8N·m; the contact resistance rose from 0.05Ω to 0.2Ω and at 30A the dissipation went from 45W to 180W, exceeding the temperature limit.
[Design Omission] No torque screwdriver, no specified torque value, and no re-tightening.
① Torque specification: tighten to the torque marked on the terminal → firm clamping
② Torque driver: use a preset torque screwdriver → accurate
③ Re-tightening: re-tighten within the first month of service → prevent loosening
④ Temperature-rise measurement: check the terminal rise <40K → confirmation
⑤ Contact resistance: measure <0.05Ω → confirmation
⑥ Oxide removal: dismantle and grind the oxidized surface → restore
⑦ Infrared survey: measure the temperature with an IR camera → early warning
⑧ Write the torque specification into the work instruction → control at the source
GB/T 14048.7-2016 Low-voltage switchgear and controlgear — Ancillary equipment — Terminal blocks for copper conductors