E45-239 · Wiring and Terminals · Outdoor Junction Box · ★
A copper wire was in direct contact with an aluminum terminal; after half a year the contact surface had white powder and the signal became unstable
[Mechanism] The potential difference between copper and aluminum, about 0.65V, forms a galvanic cell in a damp environment; the aluminum acts as the anode and corrodes into insulating aluminum-oxide powder, the contact resistance rises sharply and finally opens the circuit.
[Calculation] The 0.65V potential difference drives the corrosion current; aluminum corrodes at up to 0.1mm per year and the contact resistance rises tenfold in half a year, making the signal intermittent.
[Design Omission] No copper-to-aluminum transition terminal, no insulating seal, and no isolation from moisture.
① Transition terminal: use a transition terminal between copper and aluminum → break the potential difference
② Paste seal: coat and seal the contact surface with conductive paste → keep out moisture
③ Insulating seal: heat-shrink and seal the joint → no ingress
④ Same material: connect like materials → no corrosion
⑤ Periodic inspection: check for no white powder → early prevention
⑥ Dry conditions: add desiccant to the box → lower humidity
⑦ Contact measurement: check the resistance is stable → confirmation
⑧ Write the copper-to-aluminum transition into the specification → control at the source
GB/T 25295-2010 Guidelines for safety design of electrical equipment