Knowledge Base › Electrical Sensor Error Case › Tangled Wiring Causing a Short

Tangled Wiring Causing a Short

E45-240 · Wiring and Terminals · Inside the Control Cabinet · ★

Problem Description

Unbundled wires tangled with each other; once the insulation wore through, the adjacent 24V and 0V shorted and blew the fuse

Root Cause

[Mechanism] Loose wires rubbed against each other under cabinet vibration; the insulation wore thin and punctured, two wires at different potentials touched and shorted, and the high current blew the fuse or tripped the supply protection.
[Calculation] Insulation 0.6mm thick wears through after 100,000 rubs; at the instant of the short the fuse limits the current, but without protection the wire would burn up.
[Design Omission] No wire duct, no bundling, power and low-level circuits mixed together, and no clearance.

Corrective Solution

① Wire duct: run the wires in a duct and secure them → no rubbing
② Cable ties: bundle the loose wires → no swinging
③ Separation: run power and low-level circuits in separate ducts → isolate
④ Clearance: keep wires at different potentials ≥10mm apart → no contact
⑤ Insulation check: check for no damaged sheath → early prevention
⑥ Fuse sizing: fit the circuit with a suitable fuse → limit the current
⑦ Short-circuit alarm: trip the protection immediately on a short → early warning
⑧ Write the wiring rules into the drawing → control at the source

Checklist

Reference

GB/T 3797-2016 Electrical control equipment

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »