E45-241 · Wiring and Terminals · Terminal-Block Wiring · ★
The strip length was 15mm; the bare copper extended past the terminal clamp and touched the adjacent position, shorting
[Mechanism] The strip length exceeded the terminal's clamping zone, so the excess bare copper stuck out beyond the clamp; with the bare strand at a different potential only a hair away from the neighbouring terminal, vibration or contamination caused a short.
[Calculation] With 15mm stripped but only 8mm clamped, 7mm of bare wire was left exposed and hanging; the gap to the neighbouring position was <2mm, so with contamination the leakage current caused tracking and a short.
[Design Omission] The strip length was not specified, no strip gauge, and the wrong terminal size was chosen.
① Strip rule: strip length = clamp length + 1mm → no exposed copper
② Strip tool: use a preset-length stripping tool → accurate
③ Terminal matching: choose a terminal whose clamp zone matches → fully enclosed
④ Bare-length check: exposed copper ≤1mm → confirmation
⑤ Clearance: keep ≥2mm to the neighbouring position → no contact
⑥ Heat shrink: fit heat shrink over the end → insulation
⑦ Visual inspection: check for no long bare sections → early prevention
⑧ Write the stripping rules into the process → control at the source
GB/T 13140.1-2008 Connecting devices for low-voltage circuits for household and similar purposes