24V and 220V terminals were adjacent on the same block; an insulation breakdown destroyed the low-voltage module
[Mechanism] Power and low-level circuits were not separated onto different blocks; a transient overvoltage on the high-voltage terminal coupled to the adjacent low-level terminal by tracking or air breakdown and punctured the low-voltage module, which was not rated for that voltage.
[Calculation] A 2kV surge on the 220V side across 2mm of air gives a field of 1000V/mm, exceeding the 300V/mm breakdown strength; the air breaks down and conducts to the low-level terminal.
[Design Omission] Power and low-level circuits not separated, no safety clearance, and no isolation.
① Separation: put power and low-level circuits on separate blocks → isolate
② Safety clearance: keep low-level circuits ≥6mm from power → no breakdown
③ Isolation: add optical isolation on the low-level end → resist surges
④ Barrier: fit an insulating barrier between them → separate
⑤ Withstand test: test the low-level terminal's withstand voltage → confirmation
⑥ Surge protection: add TVS devices on the power side → suppress surges
⑦ Wiring review: review the layout → conform
⑧ Write the separation rules into the drawing → control at the source
GB/T 14048.1-2012 Low-voltage switchgear and controlgear — Part 1: General rules