E45-252 · Wiring and Terminals · Layered Cabinet Wiring · ★
The signal cable was mistakenly run in the power layer; motor start/stop made the analog input reading spike
[Mechanism] The layered-routing rule was not followed: the analog signal cable ran parallel to power cables in the same layer, and the sudden current change in the power cable induced a transient voltage spike in the signal cable through mutual inductance.
[Calculation] Over a 1m parallel run with di/dt=100A/ms and a mutual inductance M=0.1μH, the induced voltage e=M·di/dt=10mV is a spike that exceeds the resolution of the analog input and makes counts jump.
[Design Omission] No layer separation, no perpendicular crossing, and insufficient spacing.
① Layered routing: put signal and power in separate ducts and layers → isolate
② Perpendicular crossing: where they must cross, cross at right angles → less coupling
③ Clearance: keep the parallel distance ≥200mm → no induction
④ Shielded twisted pair: use shielded twisted pair for signals → resist induction
⑤ Spike test: check for no transient spikes → confirmation
⑥ Power filtering: add absorbers on the power lines → slower transitions
⑦ Routing review: review the drawing for layer separation → conform
⑧ Write the layer-separation rule into the drawing → control at the source
GB/T 3797-2016 Electrical control equipment