E45-263 · Wiring and Terminals · Signal Wire Coiled on Conduit · ★
The signal wire was coiled into several loops on site, and the magnetic field of a nearby motor induced an interference voltage
[Mechanism] Excess signal wire was loosely coiled into a loop, forming an effective number of turns; the alternating magnetic field nearby cuts the loop area and the induced EMF is added into the signal circuit.
[Calculation] With 3 turns, a 10cm² area and a 5mT field at 50Hz the induced voltage is e=N·2πfBA=3×314×0.005×0.01=0.047mV; small, but added to a microvolt signal it distorts the reading.
[Design Omission] Excess wire was not bundled, loops were not avoided, and no distance from the magnetic field.
① No loops: run excess wire straight, not in loops → no turns
② Bundle it: bundle excess wire flat → no induction
③ Away from the field: keep ≥300mm from motors → lower the field
④ Shielded twisted pair: use shielded twisted pair → resist induction
⑤ Induction measurement: check for no induced voltage → confirmation
⑥ Routing review: review the excess-wire routing → conform
⑦ Field survey: survey the surrounding magnetic field → early warning
⑧ Write the excess-wire rules into the drawing → control at the source
GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields