Knowledge Base › Electrical Sensor Error Case › Terminal Over-Torqued and Cracked

Terminal Over-Torqued and Cracked

E45-262 · Wiring and Terminals · Plastic Terminal Body · ★

Problem Description

Excessive screw torque cracked the terminal body; the wire came loose and shorted

Root Cause

[Mechanism] Tightening beyond the rated torque cracks the plastic terminal body; the clamping mechanism fails, the wire escapes, and adjacent terminals short together.
[Calculation] Applying 2.0N·m against a rating of 0.8N·m pushes the body past yield and cracks it; the clamping force falls to zero and the wire drops out.
[Design Omission] No torque tool, no torque marking, and tightening by feel.

Corrective Solution

① Torque specification: tighten to the marked value → no cracking
② Torque driver: use a preset torque screwdriver → accurate
③ Visual inspection: check the body for no cracks → confirmation
④ Clamping check: after tightening the wire must not turn → secure
⑤ Torque-limiting terminals: choose terminals with torque limiting → prevent over-tightening
⑥ Replacement: replace cracked bodies at once → no delay
⑦ Training: brief the torque value → no exceeding
⑧ Write the torque specification into the work instruction → control at the source

Checklist

Reference

GB/T 14048.7-2016 Low-voltage switchgear and controlgear — Ancillary equipment — Terminal blocks for copper conductors