E45-261 · Wiring and Terminals · Temporary Field Wiring · ★
Stranded wire was pressed straight into the terminal without preparation; in long-term service some strands broke and the contact became poor
[Mechanism] Once the stranded wire fans out, only some strands are pinched by the screw; the unclamped strands carry more load and break easily, and as more strands break the effective cross-section shrinks and the contact resistance rises.
[Calculation] Going from 19 strands to 10 cuts the cross-section by 47% and nearly doubles the current density; the contact heating makes the remaining strands break even faster.
[Design Omission] No crimped ferrule, no tinning, and non-conforming terminations.
① Crimped ferrule: always crimp a ferrule onto stranded wire → full clamping
② Tinning alternative: or tin the end into a solid core → no fanning
③ Strand check: after crimping verify all strands are in → confirmation
④ Contact measurement: check the resistance holds <0.05Ω → secure
⑤ Pull test: pull-out force ≥50N → confirmation
⑥ Periodic inspection: check for no broken strands → early prevention
⑦ Process rule: document the termination process → conform
⑧ Write the termination practice into the work instruction → control at the source
GB/T 19678.1-2010 Bare terminals, wire-end ferrules and conduits — Technical requirements and tests