E45-270 · Wiring and Terminals · Differential Input Signal · ★
One of the two differential lines was grounded and the other left floating; the common-mode voltage exceeded the interface range and caused damage
[Mechanism] One end of the differential signal was wrongly tied to signal ground while the other floated; the unequal ground potentials made the common-mode voltage far exceed the ±7V the interface allows, and the input stage broke down.
[Calculation] A 10V ground-potential difference exceeds the ±7V limit; the input protection diodes conduct and the resulting high current destroys the front-end stage.
[Design Omission] No isolation, no balancing, and no common-mode limiting were provided.
① Balanced connection: put both differential ends on the same reference → low common mode
② Isolation: add an isolation amplifier at the front end → break the ground loop
③ Common-mode limiting: limit the common mode to ≤±7V → stay within range
④ Floating-end handling: treat both ends the same way → no floating end
⑤ Protection: add clamping diodes → no burnout
⑥ Common-mode measurement: measure the ground-potential difference between the two ends → confirmation
⑦ Damage inspection: check the input stage → replace early
⑧ Write the differential wiring into the drawing → control at the source
GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields