Knowledge Base › Electrical Sensor Error Case › Terminal Overheating, Excessive Temperature Rise

Terminal Overheating, Excessive Temperature Rise

E45-269 · Wiring and Terminals · High-Current Busbar · ★

Problem Description

The temperature rise at the busbar terminal joint reached 70K and the insulation softened and deformed

Root Cause

[Mechanism] The busbar contact surfaces were poorly prepared or under-torqued, so the contact resistance was too high; the heat from the sustained high current pushed the temperature rise past the limit and the insulation softened and degraded faster.
[Calculation] A contact resistance of 0.05Ω at 50A dissipates 125W; the temperature rise ΔT≈Rθ·P reaches 70K, exceeding the insulation's rating and causing deformation.
[Design Omission] No plated surfaces, no torque achieved, and no temperature-rise evaluation.

Corrective Solution

① Plating: tin-plate the contact surfaces → lower resistance
② Torque: tighten the bolts to the specified torque → firm clamping
③ Temperature-rise check: verify the rise <40K → within limits
④ Infrared survey: measure the joint temperature with an IR camera → early warning
⑤ Contact measurement: measure <0.03Ω → confirmation
⑥ Current check: rating ≥1.2 times the load → margin
⑦ Insulation check: check for no softening → replace early
⑧ Write the temperature-rise check into the drawing → control at the source

Checklist

Reference

GB/T 14048.1-2012 Low-voltage switchgear and controlgear — Part 1: General rules