E45-268 · Wiring and Terminals · Shielded Twisted Pair · ★
The twisted pair was untwisted too far at the terminal; common-mode rejection was lost and the noise increased
[Mechanism] Untwisting too much of the pair means the untwisted section no longer cancels mutual inductance; an external magnetic field induces unequal potentials in the two wires, which becomes differential-mode noise and defeats the common-mode rejection.
[Calculation] With a 50mm untwisted length in a 5mT field the induced differential-mode voltage e=2πfBA≈0.1mV, exceeding the resolution of a microvolt-level signal and making the reading jitter.
[Design Omission] The untwisted length was not controlled, there was no twisting close to the terminal, and no shielding.
① Short untwisted length: keep it ≤10mm → preserve the twist
② Twist close in: keep the twist until right at the terminal → reject common mode
③ Shielded twisted pair: use shielded twisted pair throughout → suppress noise
④ Common-mode measurement: verify the rejection ≥60dB → confirmation
⑤ Noise measurement: verify the reading does not jitter → confirmation
⑥ Routing review: review the untwisted sections → conform
⑦ Away from fields: keep away from interference sources → reduce
⑧ Write the untwisting requirement into the process → control at the source
GB/T 17626.6-2017 Electromagnetic compatibility - Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields