E45-267 · Wiring and Terminals · Suspended Terminal Block · ★
The terminal block was held only by its clip; under vibration the whole block shifted and pulled the wires until they broke
[Mechanism] The mounting-rail clip was not locked or the rail itself was not fixed; vibration shifted the whole block and stretched the attached wires until they snapped.
[Calculation] A 3mm block displacement stretches the wires past yield; the copper strands fail after about 30,000 cycles and the adjacent measuring points lose their signals together.
[Design Omission] The clip was not locked, the rail was not fixed, and no vibration resistance was provided.
① Lock the clip: lock the block clip fully → no shifting
② Fix the rail: secure both ends of the rail → stable
③ End stops: fit end stops at both ends of the block → limit travel
④ Vibration test: simulate vibration and check for no shifting → confirmation
⑤ Slack wiring: leave slack in the wires so they are not taut → absorb vibration
⑥ Displacement inspection: check the block position periodically → early prevention
⑦ Group alarm: alarm when several points fail together → early warning
⑧ Write the block mounting into the drawing → control at the source
GB/T 14048.7-2016 Low-voltage switchgear and controlgear — Ancillary equipment — Terminal blocks for copper conductors