E45-266 · Wiring and Terminals · Lead of Moving Equipment · ★
The unsecured lead swung with the equipment and rubbed against the bracket; after half a year the insulation wore through and short-circuited
[Mechanism] The lead of the moving equipment was neither secured nor protected; during operation it repeatedly scraped against the metal bracket, the insulation gradually wore thin, and the conductor was finally exposed and shorted.
[Calculation] Insulation 0.8mm thick wears through after 200,000 rubs; the short circuit trips the circuit fuse and stops the equipment.
[Design Omission] No protective conduit, no securing, and no keeping away from sharp edges.
① Protective conduit: sleeve the lead in corrugated conduit → no chafing
② Secure it: tie the lead to a stationary point → no swinging
③ Away from sharp edges: route clear of sharp corners → no scraping
④ Insulation check: check for no broken sheath → early prevention
⑤ Clearance: keep ≥10mm from the bracket → no contact
⑥ Fuse sizing: fit the circuit with a suitable fuse → limit the current
⑦ Short-circuit alarm: trip immediately on a short → early warning
⑧ Write the moving-lead rules into the drawing → control at the source
GB 50168-2018 Standard for construction and acceptance of cable line installation in electrical equipment installation engineering