Terminal Tracking Caused by Contamination

E45-272 · Wiring and Terminals · Dusty-Environment Terminals · ★

Problem Description

Conductive dust settled between the terminals and formed a leakage path that drifted the low-level signal

Root Cause

[Mechanism] Metal or carbon dust builds up between adjacent terminals and, once damp, forms a conductive bridge; the leakage current shunts the signal, making the reading low and varying with humidity.
[Calculation] The conductance of the dust layer lets a leakage current of 0.1mA flow between adjacent terminals; across the 10kΩ signal-source impedance this produces a 1V drop and drifts the reading.
[Design Omission] No dust-proof terminals were selected, no cleaning was scheduled, and no sealing was provided.

Corrective Solution

① Dust-proof terminals: choose terminals with barriers → block dust
② Sealing cover: fit dust caps on the terminals → no buildup
③ Periodic cleaning: blow out the dust → early prevention
④ Insulation measurement: measure >10MΩ → confirmation
⑤ Dry conditions: reduce humidity inside the cabinet → no conduction
⑥ Clearance: increase the creepage distance → no bridging
⑦ Dust inspection: check for no dust buildup → clean early
⑧ Write the dust-proof requirement into installation → control at the source

Checklist

Reference

GB/T 14048.1-2012 Low-voltage switchgear and controlgear — Part 1: General rules