E45-273 · Wiring and Terminals · Spare-Core Misuse · ★
A spare core was mistakenly used as the signal core; in fact it was already connected elsewhere, creating a cross-circuit
[Mechanism] A spare core of the multi-core cable was not labeled at either end and was already connected to another circuit; using it wrongly ties it to the existing circuit, so the signal is shunted or a foreign source is coupled in, giving abnormal readings.
[Calculation] The misused core is in parallel with the original circuit; the signal-source impedance is bypassed, easily making the reading 30% low and fluctuating with the load.
[Design Omission] The spare core was not labeled, no continuity check was done, and the drawing was unclear.
① Core labeling: label both ends of every core → no confusion
② Continuity check: test that the core is independent before use → confirmation
③ Wire to the drawing: use the specified core per the drawing → accurate
④ Spare-core handling: leave unused cores floating and insulated at both ends → no mistakes
⑤ Two-person check: two people check critical cores → no mistakes
⑥ Test reading: read near zero before use → confirmation
⑦ Clear records: file the core allocation → traceability
⑧ Write the core management into the process → control at the source
GB 50168-2018 Standard for construction and acceptance of cable line installation in electrical equipment installation engineering