E45-274 · Wiring and Terminals · Long-Term Heavy-Load Terminal · ★
Long-term compression relaxes the spring of a heavy-load terminal; the reduced clamping force lets the wire fret and break
[Mechanism] Continuous high-current heating of a heavy-load terminal anneals and relaxes the spring material, lowering the clamping force; under the reduced pressure the wire frets and wears until it breaks and opens the circuit.
[Calculation] Annealing drops the clamping force from 12N to 4N and raises the contact resistance from 0.02Ω to 0.4Ω; the signal becomes intermittent and finally breaks.
[Design Omission] No heat-resistant spring was selected, no periodic replacement was scheduled, and the heating was not evaluated.
① Heat-resistant spring: choose a heat-resistant spring terminal → no annealing
② Periodic replacement: replace the terminal at end of life → no loosening
③ Contact measurement: check the resistance holds <0.05Ω → confirmation
④ Temperature-rise measurement: check the temperature rise <40K → no overheating
⑤ Re-tightening: re-compress periodically → restore the force
⑥ Break alarm: alarm immediately on a break → early warning
⑦ Life check: follow the thermal life limit → replace early
⑧ Write the terminal life into maintenance → control at the source
GB/T 14048.7-2016 Low-voltage switchgear and controlgear — Ancillary equipment — Terminal blocks for copper conductors