E45-275 · Calibration · Pressure Transmitter · ★
The zero was not calibrated; after a 20℃ ambient rise the zero drifted from 4mA to 4.8mA and readings ran about 4%FS low
[Mechanism] A diffused-silicon chip has a temperature coefficient of about ±0.02%FS/℃; without zero calibration a zero offset already exists at room temperature, the temperature rise amplifies it, and the reference point shifts with temperature.
[Calculation] A 20℃ rise introduces a zero offset of 0.02%×20=0.4%FS; adding the original 0.2% offset gives 0.6%FS, equivalent to a 0.8mA rise in the 4mA signal.
[Design Omission] No power-on self-zeroing, no periodic calibration, and no temperature compensation were provided.
① Power-on self-calibration: auto-zero on every power-up → remove the room-temperature zero offset
② Temperature compensation: correct the zero drift with a built-in temperature sensor → error <0.1%FS for a 20℃ rise
③ Periodic calibration: calibrate the zero monthly → catch drift early
④ Three-point calibration: calibrate at 0/50%/100% → accurate over the whole range
⑤ Isothermal calibration: hold the calibration environment at 20±1℃ → stable reference
⑥ Zero-drift monitoring: alarm above 0.2% → early warning
⑦ On-site recheck: re-calibrate the zero after commissioning → track the site temperature conditions
⑧ Write the calibration into the maintenance card → control at the source
GB/T 17614.1-2015 Industrial process control systems - Transmitters - Part 1: Methods of evaluating the performance