E45-276 · Calibration · Differential-Pressure Transmitter · ★
Calibrating with a single full-scale point, the measured mid-point deviated by 3%FS and the flow calculation was distorted
[Mechanism] The sensor output is nonlinear; single-point calibration corrects only the zero and span, leaving the mid-range curvature uncorrected, so the linear assumption deviates from the actual curve.
[Calculation] The actual characteristic is y=0.98x+0.02x²; single-point calibration assumes a linear 0.98x, giving an error of 0.02×0.25=0.5%FS at the 50% point, which with the zero error reaches 3%.
[Design Omission] No multi-point calibration was done and no nonlinearity correction table was built.
① Multi-point calibration: five-point calibration at 0/25/50/75/100% → fully corrected curve
② Correction table: store nonlinear correction coefficients → remove the curvature error
③ Fitting: least-squares fitting → residual <0.1%FS
④ Piecewise calibration: piecewise linear over intervals → accurate mid-range
⑤ Recheck: compare on actual flow after calibration → verify accuracy
⑥ Out-of-tolerance alarm: alarm when the deviation >0.5% → early warning
⑦ Periodic calibration: re-calibrate every quarter → track drift
⑧ Write the calibration method into the procedure → control at the source
JJG 882-2019 Verification Regulation of Pressure Transmitters