Knowledge Base › Electrical Sensor Error Case › Wrong Multi-Point Calibration Curve

Wrong Multi-Point Calibration Curve

E45-289 · Calibration · Differential-Pressure Transmitter · ★

Problem Description

At five-point calibration the points were taken out of order; the distorted fitted curve makes the mid-range deviate by 2%FS

Root Cause

[Mechanism] Multi-point calibration points were taken out of order or missed, so the fitting algorithm built a curve from wrong data; the distorted curvature amplifies the deviation between the measured points.
[Calculation] Missing the 50% point raised the fitting residual from 0.1% to 2%FS, and the mid-range deviates along the wrong curve.
[Design Omission] The point order was not specified and the fitting residual was not evaluated.

Corrective Solution

① Ordered calibration: calibrate in the order 0/25/50/75/100% → complete points
② Residual check: fitting residual <0.1% → true curve
③ Missing-point alarm: alarm when points are insufficient → prevent omissions
④ Recheck: compare the mid-points after calibration → verify accuracy
⑤ Re-calibration: re-calibrate on distortion → correct the deviation
⑥ Records: keep the point data on file → traceability
⑦ Periodic calibration: calibrate every quarter → prevent drift
⑧ Write the point-selection rule into the procedure → control at the source

Checklist

Reference

JJG 882-2019 Verification Regulation of Pressure Transmitters