E45-307 · Calibration and Adjustment · Pressure Transmitter · ★★
bar and MPa are mixed during calibration; the full-scale coefficient is off by 10 times and the reading is spuriously high
[Mechanism] The unit of the standard pressure fed in for calibration differs from the unit of the sensor range (e.g. standard in bar, range in MPa); a missed conversion puts the coefficient off by an order of magnitude.
[Calculation] 1bar=0.1MPa; mistaking 10bar for 10MPa puts the coefficient off by 10 times and the full-scale reading comes out 10 times too high.
[Design Omission] Units were not unified and the conversion was not checked.
① Unit unification: unify the units before calibration → no mixing
② Conversion check: check the bar/MPa conversion → correct value
③ Two-person check: have two people check the coefficient entry → no entry errors
④ Verification: compare at the full-scale point after calibration → verify the order of magnitude
⑤ Out-of-tolerance alarm: warn when the deviation >2% → early warning
⑥ Records: keep the units on file → traceability
⑦ Recalibration: recalibrate when wrong → correct the bias
⑧ Write the unit requirement into the procedure → control at the source
GB/T 17614.1-2015 Industrial process control systems - Transmitters - Part 1: Methods of evaluating the performance