E45-310 · Calibration and Adjustment · Differential Pressure Transmitter · ★
Only two points are calibrated; the mid-range nonlinearity goes uncorrected, off by 2%FS
[Mechanism] Too few calibration points cannot capture a nonlinear curve; assuming a straight line between two points leaves the mid-range curvature deviation uncorrected.
[Calculation] Two-point calibration misses the mid range; the true curvature of 2%FS is fully biased in the middle segment.
[Design Omission] No multi-point calibration was done and the number of points was not worked out.
① Multi-point calibration: calibrate at least five points → full curve
② Residual check: keep the fitting residual <0.1% → true fit
③ Point-count alarm: alarm when points are insufficient → prevent omissions
④ Verification: compare at intermediate points → confirm accuracy
⑤ Re-calibration: re-calibrate on distortion → correct the deviation
⑥ Records: keep the point data on file → traceability
⑦ Periodic calibration: calibrate every quarter → prevent drift
⑧ Write the point requirement into the procedure → control at the source
JJG 882-2019 Verification Regulation of Pressure Transmitters