A transmitter mounted tight against a steam pipe has a body temperature of 95℃, above the 70℃ rating; the zero drifts by 3%FS and the reading keeps climbing
[Mechanism] Electronic components drift in parameter at above-rated temperatures; the op-amp offset voltage grows as temperature rises, the zero drifts with it, and it does not self-recover.
[Calculation] The rating is 70℃ but the actual is 95℃, 25℃ over; at a temperature drift of 0.1%FS/℃ the zero drift is estimated at 2.5%FS, matching the measured 3%.
[Design Omission] The installation did not assess radiant and conducted heat, and no insulation or cooling measure was added.
① Temperature matching: body at 95℃ over rating → add a heat sink to bring the case temperature down to ≤65℃, back into the rated range
② Insulated mounting: add a thermal-break bracket between the transmitter and the hot pipe → cut the conduction path
③ Remote pressure connection for cooling: use a capillary remote-seal type to move the electronics cavity away from the heat source → the body no longer sees high temperature
④ Heat shielding: add a reflective baffle to block radiant heat → reduce radiant heating
⑤ Choose a high-temperature type: switch to an 85℃-rated industrial model → increase the rating margin
⑥ Temperature monitoring: built-in case-temperature monitoring alarms at >80℃ → early warning of overtemperature
⑦ High-temperature verification: measure the case temperature in service to confirm ≤ rating → verify with data
⑧ Selection standardization: write the ambient temperature and mounting method into the selection table → control at the source
GB/T 17614.1-2015 Industrial process control systems - Transmitters - Part 1: Methods of evaluating the performance