E45-336 · Environmental Protection and Temperature/Humidity · Proximity Switch · ★★★
A non-explosion-proof sensor is wrongly used in a methane area; contact sparks risk ignition, and the housing is not corrosion-resistant
[Mechanism] The make-break contacts of a non-explosion-proof sensor produce electric sparks; when the methane concentration reaches the explosive limit they can ignite and detonate, posing a major safety hazard.
[Calculation] The lower explosive limit of methane is 5%; the contact spark energy is on the order of mJ, far above methane's minimum ignition energy of 0.28mJ, meeting the conditions for ignition.
[Design Omission] The area hazard classification was not assessed, and the selection did not follow explosion-proof requirements.
① Explosion-proof selection: in a methane area → choose an Ex d flameproof or Ex ia intrinsically safe type → sparks contained / energy limited
② Intrinsically safe circuit: add a safety barrier to limit energy → circuit energy below the ignition energy
③ Flameproof enclosure: use a flameproof junction box → internal sparks are contained
④ Grounding and equipotential bonding: explosion-proof grounding ≤4Ω → drain static
⑤ Certification check: verify the Ex certification matches the area classification → compliance
⑥ Gas monitoring: add a combustible-gas alarm interlock → cut power when the limit is exceeded
⑦ Explosion-proof verification: check the Ex marking and certificate before installation → data confirmation
⑧ Selection standardization: write the area hazard classification into the selection mandatory list → control at the source
GB/T 3836.1-2021 Explosive atmospheres - Part 1: Equipment - General requirements