E45-337 · Environmental Protection and Temperature/Humidity · Level Switch · ★★
Condensate from a cold pipe accumulates on the probe and freezes; the ice layer jams the float, distorting the level reading
[Mechanism] The cold pipe makes the water vapor in the air condense and freeze on the probe; the ice envelops the mechanical parts and jams the float so it cannot move with the level.
[Calculation] A pipe temperature of -5℃ is below the dew point, so condensation is inevitable; within hours an ice layer several mm thick jams the float travel.
[Design Omission] No anti-freeze heat tracing was provided, and the probe was exposed to freezing duty.
① Heat-tracing anti-freeze: add electrical heat tracing to the probe to keep it >0℃ → prevent freezing
② Insulation wrapping: wrap the probe section in insulation → reduce condensation
③ Freeze-proof construction: choose a capacitive/radar type with no moving parts → no jamming points
④ Drainage design: provide a drain at the low point → condensate does not accumulate
⑤ Temperature monitoring: alarm when probe temperature <2℃ → warn before freezing
⑥ Dry isolation: desiccant in the cavity → reduce internal condensation
⑦ Low-temperature verification: run a freezing-duty test to confirm operation → data confirmation
⑧ Selection standardization: write freezing duty into selection and heat-tracing requirements → control at the source
GB/T 4208-2017 Degrees of protection provided by enclosures (IP code)