E45-349 · Environmental Protection and Temperature/Humidity · Rain Gauge Sensor · ★★
During a downpour the junction-box cable entry was not sealed; rainwater poured in, shorting the terminals and corrupting the data
[Mechanism] The cable entry of the junction box was not sealed; in heavy rain water runs along the cable or through the openings into the box, submerges the terminals, and shorts them.
[Calculation] At a rainfall intensity of 100mm/h an unsealed opening lets in tens of mL per hour; submerging the terminals drops the insulation to zero.
[Design Omission] Junction-box protection and cable-entry sealing were missing.
① Cable-entry sealing: seal the entry with a waterproof gland and plug → block the water path
② Drip loop at the outlet: form a U-shaped drip loop in the cable → water drips off the cable instead of entering the box
③ Enclosure rating: choose an IP66 junction box → withstand heavy rain
④ Potting inside the box: pot the terminal area → even slight seepage will not short the circuit
⑤ Bottom drainage: fit a vented drain valve at the box bottom → drain accumulated water
⑥ Insulation monitoring: alarm when <10MΩ → detect water ingress early
⑦ Rain verification: run an IP66 rain test to confirm → data confirmation
⑧ Selection standardization: write outdoor junction-box protection into the installation spec → control at the source
GB/T 4208-2017 Degrees of protection provided by enclosures (IP code)