E45-358 · Environmental Protection and Temperature/Humidity · Proximity Sensor · ★★★
The drain hole at the bottom of an outdoor proximity switch's guard is blocked; rainwater collects and soaks the sensor, causing water ingress, a short, and false operation
[Mechanism] The guard is meant to drain, but once the drain hole is clogged with mud and sand the rainwater collects; prolonged soaking breaks the seal and lets water in, shorting the device.
[Calculation] Water collects to 30mm deep inside the guard, submerging the sensor terminals; the insulation resistance drops from 100MΩ to 0.5MΩ and false operation is triggered.
[Design Deficiency] The drain hole's orientation or diameter made it easy to clog, and there was no anti-clog design.
① Drainage optimization: put the drain hole at the lowest point and enlarge it → smooth drainage
② Anti-clog screen: add a stainless-steel insect-proof, clog-proof screen at the drain → block mud and sand
③ Tilted mounting: tilt the guard slightly so water runs off → no accumulation
④ High-protection selection: choose an IP67 fully sealed sensor → withstand brief immersion
⑤ Potting: epoxy-pot the terminals → isolate against water ingress
⑥ Water accumulation monitoring: add a leak-detection alarm inside the guard → timely detection
⑦ Immersion verification: run an IP67 immersion test to confirm → data confirmation
⑧ Selection standardization: write the outdoor water-accumulation risk into the protection selection criteria → control at the source
GB/T 4208-2017 Degrees of protection provided by enclosures (IP code)