Knowledge Base › Electrical Sensor Error Case › Outdoor Day-Night Temperature Swing Loosens the Wiring and Causes Poor Contact

Outdoor Day-Night Temperature Swing Loosens the Wiring and Causes Poor Contact

E45-357 · Environmental Protection and Temperature/Humidity · Pressure Sensor · ★★

Problem Description

On an outdoor pressure transmitter with a large day-night temperature difference, the terminals' repeated thermal expansion and contraction loosen the screws, making the signal jump and drift intermittently

Root Cause

[Mechanism] The day-night temperature difference makes the terminal and the wire micro-move repeatedly because their thermal expansion coefficients differ; the screw gradually loosens and the contact resistance rises.
[Calculation] With an outdoor day-night temperature difference of 40℃, the accumulated expansion difference between copper and steel makes the contact pressure fluctuate cyclically and loosens the screw by 0.1 turn per month.
[Design Deficiency] Ordinary screw terminals were used with no locking provision, and the temperature cycling was not considered.

Corrective Solution

① Locking terminals: choose spring-cage, screw-free terminals → resist temperature-induced loosening
② Lock washers: add disc-spring washers under the screws to compensate for expansion → maintain contact pressure
③ Threadlocker: apply medium-strength threadlocker to the terminal screws → prevent loosening
④ Flexible slack: leave an expansion bend in the wire to reduce tensile stress → less micro-movement
⑤ Sunshade to reduce the temperature difference: add a sunshade to narrow the day-night difference → less expansion and contraction
⑥ Regular tightening: include torque rechecks in the inspection plan → timely detection
⑦ Thermal-cycle verification: run a temperature cycling vibration test to confirm → data confirmation
⑧ Selection standardization: write the outdoor temperature difference into the terminal selection criteria → control at the source

Checklist

Reference

GB/T 2423.22-2012 Environmental testing for electric and electronic products - Test for temperature change