E45-356 · Environmental Protection and Temperature/Humidity · Humidity Sensor · ★★
A temperature/humidity probe at a cold-store doorway is frequently exposed to warm, moist air and condenses; the water film freezes over the sensing element, making the reading stay high and lock up
[Mechanism] Warm, moist air meets the cold probe and condenses; at low temperature the water film freezes into an ice shell that covers the sensing film and disables the response.
[Calculation] Air at 25℃/80%RH meeting a -18℃ surface must condense and freeze; the ice shell locks the humidity reading above 95%RH.
[Design Deficiency] The condensation zone at the doorway caused by the temperature difference was not evaluated, and the probe had no anti-condensation measures.
① Anti-condensation type: choose a humidity probe with heating to clear condensation → suppress icing
② Sheltered placement: keep away from the airflow zone where cold and warm air meet at the doorway → less condensation
③ Slight heating: heat the sensing film at low power above the dew point → prevent icing
④ Protective filter: add a hydrophobic, breathable sintered cover → keep out the water film
⑤ Scheduled defrost: heat in sync with the cold store's defrost cycle → melt the ice shell
⑥ Redundant placement: set the main measuring point away from the doorway → protect the data
⑦ Condensation verification: run a temperature-variation condensation test to confirm → data confirmation
⑧ Selection standardization: write the condensation condition into the mandatory selection criteria → control at the source
GB/T 2423.4-2008 Environmental testing for electric and electronic products - Damp heat, cyclic test