E45-369 · Environmental Protection and Temperature/Humidity · Level Sensor · ★★★
An outdoor storage-tank level gauge breathes with the day-night temperature swing; external moisture is drawn into the inner cavity and condenses, wetting the circuit and causing false alarms
[Mechanism] Rising and falling temperature makes the gas inside the enclosure expand and contract, creating a breathing effect; unfiltered moist air is drawn in and condenses into water that collects.
[Calculation] A 30℃ day-night temperature difference expands and contracts the internal gas by about 10% of its volume; repeated moisture intake makes the cavity collect water day by day until it floods the circuit.
[Design Deficiency] There was no moisture-proof breather, and the non-airtight housing left a breathing path that drew in moisture.
① Moisture-proof breathing: add a Gore-Tex moisture-proof breather → keep out moisture
② Airtight potting: pot the circuit cavity airtight → stop the breathing
③ Dry fill: fill the cavity with dry nitrogen → no water vapor
④ Slight heating to prevent condensation: keep the cavity slightly above the dew point → prevent condensation
⑤ Condensate drain design: provide drain holes to remove collected water → prevent water buildup
⑥ Regular inspection: patrol for water inside the cavity → early detection
⑦ Temperature-change verification: run a temperature-change condensation test to confirm → data confirmation
⑧ Selection standardization: write the outdoor breathing condition into the selection criteria → control at the source
GB/T 2423.22-2012 Environmental testing for electric and electronic products - Test for temperature change